IS 456

Construction and boiler feed water testing

Water used to mix concrete is checked for the impurities that attack reinforcement or interfere with setting — chloride, sulphate, organic matter and suspended solids. Boiler feed water is checked for the impurities that cause scale, corrosion and carryover. Both are suitability tests, not safety tests.

Standard
IS 456 (concrete)
Sample needed
2 litres
Judged on
Suitability, not potability
Common use
Pre-pour approval, boiler commissioning

Water for concrete — IS 456 limits

Permissible limits for water used in mixing and curing plain and reinforced concrete under IS 456. Boiler feed water is assessed separately against the boiler manufacturer’s water chemistry specification.

ParameterUnitPermissible limitWhy
pH valueNot less than 6Acidic water attacks cement paste
Organic mattermg/L200 maxInterferes with setting and strength gain
Inorganic mattermg/L3000 maxTotal impurity load
Sulphates (as SO₃)mg/L400 maxSulphate attack on hardened concrete
Chlorides (as Cl) — reinforced concretemg/L500 maxCorrodes reinforcement steel
Chlorides (as Cl) — plain concretemg/L2000 maxNo steel to protect, so relaxed
Suspended mattermg/L2000 maxAffects water-cement ratio control

What to send us

Quantity
2 litres, taken from the point the mixer actually draws from
Container
Clean plastic container, rinsed with the same water before filling
Hold time
Not time critical for the chemical panel — within a few days is acceptable
Full collection instructions →

Test before the pour, not after

Site water is often drawn from a borewell sunk for the project, and in parts of coastal and South Bengal that water can carry chloride well above the reinforced-concrete limit. Chloride-driven corrosion does not show up for years, and by then the remedy is structural. A single test before the first major pour is the cheapest risk control on the job.

Questions about this test

Can I use borewell water for concrete?

Often yes, but it has to be tested first — particularly for chloride and sulphate. Proximity to the coast or to saline aquifers is the main risk factor, and it is not something you can judge by taste or appearance.

Is sea water ever acceptable?

Not for reinforced concrete. The chloride content is far above the IS 456 limit and will corrode reinforcement. It is sometimes tolerated in unreinforced mass concrete, but that is a design decision, not a testing one.

What do you test for boiler feed water?

Typically hardness, alkalinity, silica, chloride, dissolved oxygen indicators, TDS and conductivity — assessed against the pressure rating and the manufacturer’s specification, since a high-pressure boiler tolerates far less than a low-pressure one.